Details
-
Manufacturer : Mitsubishi Electric
-
Product No.: FX2N-48ER
-
Product type: I / O Expansion Unit
-
Application sequencer : FX1N, FX3G, FX2N, FX3U
-
Rated voltage : AC 100 V to 240 V
-
Voltage tolerance range : AC 85V ~ 264V
-
Rated frequency : 50/60 Hz
-
Power supply fuse : 250 V 5 A
-
Inrush current : AC 100 V: maximum 40 A 5 ms or less AC 200 V: maximum 60 A 5 ms or less
-
power consumption : 35W
-
24 VDC service power supply : 24 VDC 460 mA or less When connecting input / output extension block, 24 VDC service power is consumed.
-
Input specification :
-
Number of input points : 24 points
-
Input connection shape : Removable terminal block (M3 screw)
-
Input format : sink
-
Input signal voltage : DC 24 V ± 10%
-
Input impedance : 4.3 kO
-
Input signal current : 5 mA / 24 VDC
-
Input ON sensitivity current : 3.5 mA or more
-
Input OFF sensitivity current : 1.5 mA or less
-
Input response time : About 10 ms
-
Input signal format : No-voltage contact input or NPN open collector transistor
-
Input circuit insulation : Photocoupler insulation
-
Input operation display : LED on the panel when input is ON
-
Number of output points : 24 points
-
Output connection shape : Removable terminal block (M3 screw)
-
Output type / format : relay
-
External power supply : AC 250 V DC 30 V or less
-
Maximum load Resistive load : Please set the total load current per 2A / 1 point common as follows. . Output 4 points / common: 8 A or less . Output 8 points / common: 8 A or less
-
Inductive load : 80VA
-
Minimum load : DC 5 V 2 mA (reference value)
-
Response time OFF ? ON : About 10 ms
-
ON ? OFF : About 10 ms
-
Circuit insulation : Mechanical insulation
-
Output operation indication : When the relay coil is energized LED on the panel is lit
-
Ambient temperature : 0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save
-
Relative humidity : 5 to 95% RH (noncondensing).... in operation
-
Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
-
Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (80 minutes in total in total) The criterion is based on IEC 61131-2
-
Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
-
Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
-
Impact resistance : 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
-
Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 µs, rising 1 ns, with noise si
-
tor with period of 30 to 100 Hz
-
Withstand voltage : Between the power supply terminal (AC power supply) and the earth terminal: AC 1500 V for 1 minute 24 VDC Service power supply and between the input terminal (24 VDC) and the earth terminal: 500 V AC for 1 minute Between the output terminal (relay)
-
Insulation resistance : Between each terminal and earth terminal: 500 MV DC 500 MO or more with an insulation resistance meter
-
ground : Class D grounding (grounding resistance: 100 O or less)Grounding should be dedicated ground or common ground.
-
Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
-
Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.